sản phẩm Bán chạy
Trung tâm báo cháy 5 Zone Notifier SFP-5UDE
Trung tâm báo cháy 5 Zone Notifier SFP-5UDE
- The SFP-5UDE is a five-zone FACP (Fire Alarm Control Panel).
- Listed to UL Standard 864, 9th edition.
- Built-in DACT (Digital Alarm Communicator/Transmitter).
- Style B (Class B) IDC (Initiating Device Circuit): SFP-5UDE -five IDCs.
- Style Y (Class B) NAC (Notification Appliance Circuit)-special application power SFP-5UD-four NACs.
- Notification Appliances may be programmed as
+ Silence Inhibit.
+ Auto-Silence.
+ Strobe Synchronization for System Sensor, Wheelock, Gentex, Faraday, or Amseco devices.
+ Selective Silence (horn-strobe mute).
+ Temporal or Steady Signal.
+ Silenceable or Nonsilenceable.
- 3.0A total system current for SFP-5UDE.
- Optional Trim Ring TR-CE/-B for semi-flush mounting.
- 24 volt operation.
- Low AC voltage sense.
- Alarm Verification.
- PAS (Positive Alarm Sequence).
- Automatic battery trickle charger.
- Optional Remote Annunciator N-ANN-80.
- Optional Remote Printer Gateway N-ANN-S/PG.
- Optional LED Annunciator Driver N-ANN-I/O.
- Optional 4XTM module (conventional reverse polarity/city box transmitter).
Thông số kỹ thuật
Model |
SFP-10UDE |
System Capacity |
- Annunciators: 8 |
Electrical Specifications |
- Power Supply: 240 VAC, 50 HZ, 2.20 A |
Cabinet Specifications |
- Door: 19.26' (48.92 cm.) high x 16.82' (42.73 cm.) wide x |
- Backbox: 19.00' (48.26 cm.) high x 16.65' (42.29 cm.) wide x 5.25' (13.34 cm.) deep |
|
- Trim Ring (TR-CE): 22.00' (55.88 cm.) high x 19.65' (49.91 cm.) wide. |
|
Shipping Specifications |
Dimensions |
Temperature and Humidity Ranges |
This system meets NFPA requirements for operation at 0-49°C/32-120°F and at a relative humidity 93% ± 2% RH (noncondensing) at 32°C ± 2°C (90°F ± 3°F). However, the |
Agency Listings and Approvals |
The listings and approvals below apply to the basic SFP-5UD |
NFPA Standards |
The SFP-10UDE complies with the following NFPA 72 Fire Alarm Systems requirements: |