• Hotline: 0914.348.397 - 032.697.5555
  • Email: tuanthanh@anninh.com.vn
  • Thời gian làm việc từ Thứ 2 - Chủ nhật: 08:00-19:00
  • Logo

  • vi
  • en

sản phẩm

Giá tiền

Trung tâm báo cháy 5 kênh NITTAN 2PD1-5L

Trung tâm báo cháy 5 kênh NITTAN 2PD1-5L

Giá: Liên hệ

    Mã sản phẩm: 2PD1-5L
  • Bảo hành: 12 tháng
  • Xuất xứ: Nhật Bản
  • Nhãn Hiệu: Nittan

Chọn mua:

Mua hàng

    trợ giúp tư vấn khách hàng

    024.62810015
    0914 348 397 - 0326975555

Trung tâm báo cháy 5 kênh NITTAN 2PD1-5L

- The 2PD1-5L is a conventional fire alarm panel with a stylish wall-mount design supplied in 5 zone format. All detector circuits will be indicated with lighting red LEDs in alarm conditions and flushing in open circuit fault conditions. Slide-in paper labels are included for clear zone identification. The alarm panel has an alarm delay function on detector circuits to reduce false alarms, including a delay ON/OFF function.

- Alarm delay function

+ Heat Detector: 20 sec.

+ Smoke Detector: 60 sec.

- Alarm delay ON/OFF switch function

- Supervision of detector lines and fault conditions.

- Energy saving technorogy for its running cost.

- Extra slim design.

- Light body using flame retardant ACS resin.

- High reliablility minimmizes maintenance cost.

- Equipped with surge absorbers.

- Re-sounding system.

- 1 output for zone alarm bells.

- 1 output for signal transfer to external facility.

- Easy wiring by Push-in terminals’ one-touch connection.

Thông số kỹ thuật

Model

2PD1-5L

AC Power

220 VAC ±10% 50/60 Hz

Standby Battery

24VDC / 0.225 Ah, Sealed Type Ni-Cd battery

Nominal Delay Time

60 sec. (For smoke detector: 60 sec. For heat detector: 20 sec.)

Dimensions

W 240 x H330 x D 70 mm

LED Indicators

Zone alarm, AC power, Circuit voltage, Switch operation, Alarm
delay

Functions

Circuit voltage monitoring, Cable break monitoring

External Line Resistance

50 Ω and less

End of Line Device

CRE

Panel Alarm Sounder

Piezoelectric buzzer, automatic re-sounding type

Fire Alarm Transfer

  1. Contact Capacity
    Fire Alarm : F-F’ (Normally-Open) 1 A 24 VDC
    Fire Alarm: GA-GB-GC (Form-C) 1 A 24 VDC

Output Current for Zone Alarm Bells

125 mA @ 24 VDC (B-BC)

Output Current for Indication Lamps

25 VAC 300 mA (PL-PL’)

Number of Connectable Detectors

Standard type Smoke detector: Max. 20 /zone
Heat detector: As required
Thermistor type Heat detector: Max. 24 /zone, Total 12 x zones

Connectable Manual Alarm Station

2ME1A 2MH1A

Connectable Annunciator Panel

Model PSH x 1 unit

Operating Temperature

0°C to +40°C

Primary Materials

Flame retardant resin

Body Color

JPMA Color Code A22-90B Semi-gloss (off-white)