- Nittan’s SPERA NFU-7000 Network Fire Alarm Control Panel offers modular components to meet a wide variety of applications. Designed for peer-to-peer network communications, the NFU-7000 allows for a maximum of 63 nodes, while providing reliability, flexibility and expandability.

Fire Alarm Control

- One driver card capable of 2 loops is equipped as standard.

- NFU-7000 has capability of three driver cards storage (max 6 loops).

- One loop supports 254 addresses which can be wired in Class A (Style 6 or 7) or Class B (Style 4).

- Use of shielded cable is not required for SLC loops.

- Modular design.

- Four Class A/B (Style Z/Y) Notification Appliance Circuits rated at 1.7 Amps each.

- One Auxiliary power supply, rated at 1.7 Amps for 24 VDC and one resettable 4-wire power supply.

- Large 16 line x 40 character Back-lit LCD Display with user friendly menu.

- Programmable Switch Inputs which allow for multifunctional outputs.

- Four Status Queues with selector switches and LEDs for Alarm, Supervisory, Trouble and Monitor.

- Auxiliary relay contacts for Common Alarm, Common Supervisory and Common Trouble.

- RS-232 port for remote system printer.

- Two Event History Logs comprised of a 1000 alarm history log for alarm related events and a 6000 event history log for all events.

- Supports three configuration files (current, previous and next configuration) with “hot swap” support.

- Supports Conventional Hardwire Adder Modules.

- Built-in One Man Walk Test operation.

- Provides drift compensation for photoelectric smoke detectors.

- Capability to adjust sensitivity levels of intelligent smoke detectors.

- Real time 3D graphical monitoring and control by Nittan’s NFU-Graphic-monitor.

- BACnet support.

- Supports Boolean logic functions.

- Built-in Ethernet port.

- UL listed for Smoke Control.

- Manual Control Function.

- Input Simulation Function.

- Multiple group bypass function with built-in false alarm prevention technology

   + Network Node Bypass;

   + Node Outputs Bypass;

   + Input Zone Bypass;

   + Relay Disconnect;

   + Device/Circuit Bypass.

Network Features

- Up to 63 panels.

- Peer-to-peer network communications.

- Mutual surveillance/ 2 way control available.

- Class A (Style 6 or 7) or Class B (Style 4) wiring configuration.

- ARCNET protocol.

- Supports copper and/or fiber optic network cable.